Description
Product Highlights
The Fluke 1777 is a dual-purpose power quality troubleshooter and logger. It measures the fundamental power quality variables required to measurement the overall power quality health of the electrical system. It also shows the waveform detail in context with graphed RMS values and transient waveforms sampled at 20MHz. Setting up for measurements and logging is simple and reliable. Instrument powering from the measurement circuit, automatic connection check and correction
Key Attributes
- Measurement Category 600V CAT IV/1000V CAT III
- Power: Includes associate variables and assocciated variable including apparent power, kvar, energy reactive energy, power factor, cos Φ, etc. all according to IEEE1467
- Wide range of power quality variables.
- Includes dips and swells, unbalance, harmonics to 50 harmoncs, 2-9kHz and up to 30kHz, flicker, inrush and transients up to 8kV with 20MHz sampling.
- Automated logging of variables.
- Over 500 of the most frequently used variables with automated setup or this can be expanded with additional values. Values are logged with 1s to 30 minute average times. Dips, swells and transients occur in much shorter times and are recorded at much higher speed indendently of the logging average.
Key Uses of the Product
- Measure power quality according to the most stringent IEC61000-4-30 Class A requirement.
- Capture dips, swells and interruptions and the presence of transient and their cause.
- Perform harmonic studies to discover the effects of disturbing loads on your network
- Discover the sources of energy loses and waste in your facility.
Equipment is available for rental.
Contact [email protected] for rental inquiry.
Reviews
There are no reviews yet.